Application and Description:

EEF/F(EM-EEF) CEF/F(EM-CEF) cables are used for general purpose power distribution in wet or dry locations, installed in air, in conduit or duct, or directly buried.

Name Code:

E: Polyethylene

C: Cross-linked polyethylene

F : Flat type

/F: Flame retardant polyethylene

Cable Construction:

EEF/F(EM-EEF) CEF/F(EM-CEF)

Conductor: Solid or circuar stranded annealed copper wires

Seperator: A proper separator may be applied to a conductor

Insulation: Polyethylene/Cross-linked polyethylene

Color :

2 cores- Black and white

3 cores- Black, white and red

Filler: Non-hygroscopic material(optional)

Binding tape: Polyester (Mylar) tape (optional)

Sheath: Flame retardant polyethylene, Black color

Technical Characteristics:

Maximum conductor temperature 90oC

Circuit voltage not exceeding 600 volts

Cable Parameter:

NO. OF CORES NOMINAL SECTIONAL AREA NO. OF WIRE DIAMETER OF CONDUCTOR (APPROX.) THICKNESS OF INSULATION THICKNESS
OF SHEATH
OVERALL DIAMETER (APPROX.) MAXIMUM
DC.
RESISTANCE OF CDR. AT 20°C
TEST VOLTAGE CABLE WEIGHT (APPROX.)
MM² MM MM MM MM OHM / KM V KG / KM
2 1.6 Solid 1.6 0.8 1.5 6.2x9.4 8.92 1500 95
2 Solid 2 0.8 1.5 6.6x10.5 5.65 1500 120
2.6 Solid 2.6 1 1.5 7.6 x12.5 3.35 1500 180
3.2 Solid 3.2 1 1.5 8.2x13.5 2.21 1500 240
2 7/0.6 l.8 0.8 1.5 6.4 x9.8 9.24 1500 100
3.5 7/0.8 2.4 0.8 1.5 7.0x1 1.0 5.2 1500 140
5.5 7/ 1.0 3 1 1.5 8.0xI3.0 3.33 1500 195
8 7/1.2 3.6 1 1.5 8.6 x14.5 2.31 1500 250
3 1.6 Solid 1.6 0.8 1.5 6.2 x13.0 8.92 1500 135
2 Solid 2 0.8 1.5 6.6x14.0 5.65 1500 175
2.6 Solid 2.6 1 1.5 7.6x17.0 3.35 1500 265
3.2 Solid 3.2 1 1.5 8.2 x19 2.21 1500 355
2 7/0.6 l.8 0.8 1.5 6.4 x13.5 9.24 1500 140
3.5 7/0.8 2.4 0.8 1.5 7.0x15.0 5.2 1500 200
5.5 7/ 1.0 3 1 1.5 8.0x18.0 3.33 1500 285
8 7/1.2 3.6 1 1.5 8.6x20 2.31 1500 370